Permitted cable routes in Walls




This diagram shows the prescribed safe zones for concealed cables in walls.


safezones_1_.jpg

If a cable is run outside of the zones shown with green and blue then it must either be buried to a dept of 50mm or more below the finished wall surface, or comply with regulation 522-06-06 parts (i), (ii), & (iii) (see below)





If the wall is 100mm or less thick then the safe zone also extends to the other side of the wall as shown here in more detail

text_1_.jpg





Also an external link to have a browse through:


http://www.tlc-direct.co.uk/Book/4.4.1.htm -Guide to the 16th Edition IEE Regulations 4.4 - Cable supports, joints and terminations:


External links with more information on rules for concealed cables:

http://www.voltimum.co.uk/files/gb/attachments/niu/l/attachments/c5-43.pdf

http://web.archive.org/web/20061110111450/http://www.niceic.org.uk/downloads/concealedcables.pdf

IEE article

 IEE Article on new requirements for concealed cables  IMPORTANT : Click.





SKIRTING BOARDS


You must never run cables horizontally behind skirting boards unless they are enclosed in earthed, steel conduit.  Vertically from under the floor to a socket on the wall above the skirting is fine.